MZC-305 Loop Impedance Meter

Description

  • Loop impedance measurement with resolution 0,01 Ω
  • Loop impedance measurement without tripping the circuit breaker > 30 mA with resolution 0,01 Ω (100…440 V)
  • Measurements possible in installations 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 290/500 V and 400/690 V (range 100…750 V)
  • Short circuit current indication
  • Voltage measurement up to 750 V and up to 250 V with resolution 0,1 V
  • Measurements using Uni-Schuko adapter or test wires 1,2; 5; 10 and 20 m
  • Memory of 990 records
  • USB connection with PC
  • Powered by disposable or rechargeable (4xAA)

Measurement of short circuit loop impedance (ZL-PE, ZL-N, ZL-L)

Measuring range according to IEC61557: 0,13…1999 Ω for 1,2 m test leads; 0,25…1999 Ω for UNI-SCHUKO adapter

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(5% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω ±(4% m.v.. + 3 digits)
200…1999 Ω 1 Ω
  • rated operating voltage UnL-N/ UnL-L: 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 290/500 V, 400/690 V,
  • operating voltage range: 100-440 V (for ZL-PE and ZL-N) and 100-750 V (for ZL-L)
  • high current measurement (up to 30 A),
  • operating frequency range: 45…65 Hz,
  • control of correctness of PE terminal connection by means of a contact electrode (applicable to ZL-PE),
  • measurement is also possible when L and N circuits are swapped,
  • measurement of resistance and reactance components,
  • short circuit current calculation.

Measurement of short circuit loop impedance ZL-PE RCD (without RCD tripping)

Measuring range according to IEC61557: 0,43-1999 Ω for 1,2 m test leads; 0,50-1999 Ω for UNI-SCHUKO adapter

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(6% m.v. + 10 digits)
20,0…199,9 Ω 0,1 Ω ±(6% m.v. + 5 digits)
200…1999 Ω 1 Ω
  • operating voltage range: 100 – 440 V,
  • rated operating voltage Un: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V, 390 V, 400 V,
  • control of correctness of PE terminal connection by means of a contact electrode,
  • measurement is also possible when L and N circuits are swapped,
  • measurement of resistance and reactance components,
  • short circuit current calculation.

Voltage measurement

Range Resolution Accuracy
0,0 V…249,9 V 0,1 V ±(2% m.v. + 4 digits)
250 V…750 V 1 V ±(2% m.v. + 2 digits)
  • measurement available for all settings of short-circuit loop (ZL-PE, ZL-PE RCD and ZL-N,L-L),
  • frequency range 45-65 Hz,
  • overvoltage alarm.

Electrical safety:

  • type of insulation: double, according to IEC 61010 – 1
  • measurement category: CAT IV 600 V (CAT III 1000 V)
  • protection class acc. to EN 60529: IP54

Other technical data

  • power supply: alkaline batteries or NiMH rechargeable batteries, size AA (4 pcs)
  • number of Z measurements (for alkaline batteries): >3000 (2 measurements per minute)
  • time to Auto-OFF: 120 seconds
  • data transmission: USB
  • memory of measurement results: 990 cells, 3500 entries
  • display: LCD segment
  • dimensions: 260 x 190×60 mm
  • meter weight: ca. 2,2 kg

Rated operational conditions:

  • operating temperature: 0…+45°C
  • storage temperature: -20…60°C
  • humidity 20 – 80%

The instrument meets the requirements of EMC standards

Reviews

There are no reviews yet.

Be the first to review “MZC-305 Loop Impedance Meter”

Downloads

Data Sheets

 

User Manual

 

Declarations Of Conformity

More news coming soon

Courses Coming Up Soon

Like us on Facebook or subscribe to our Blog to stay up to date with upcoming training courses.