P-1 Voltage And Continuity Tester

Description

P-1 Voltage and continuity tester functionality includes:

  • AC/DC voltage indication,
  • Unipolar indication of phase,
  • Circuit continuity check,
  • Phase rotation indication,
  • RCD testing.

Specifications

  • Type of insulation: double, EN 61010 – 1 compliant
  • Safety category: III 1000 V (IV 600 V) as per EN 61010 – 1
  • Housing degree of protection as per EN 60529: IP65
  • Voltage range: 12…690 V AC/DC
  • Voltage indications: 12 V, 24 V, 50 V, 120 V, 230 V, 400 V, 690 V
  • input resistance
Uin Rin
12 V, 24 V, 50 V ~6 kΩ
120 V ~20 kΩ
230 V ~70 kΩ
400 V ~150 kΩ
690 V ~240 kΩ
  • Accuracy of voltage indications: as per EN 61243 – 3
  • Voltage frequency range: 0…400 Hz
  • Maximum current: IS<0,2 A/IS(5 s)<3,5 mA
  • Maximum work interval: 30 s
  • Minimum recovery time after being connected for 30 s: 240 s
  • Minimum voltage triggering the device: <12 V
  • Voltage range for unipolar phase indicator: 50…690 V
  • Frequency range for unipolar phase indicator: 50…400 Hz
  • Continuity test range: 0…400 kΩ
  • Continuity test accuracy: ±50%
  • Continuity test current: 3μA
  • Voltage range for bipolar phase rotation indicator: 100…690 V
  • Frequency range for bipolar phase rotation indicator: 50…60 Hz
  • Power supply: 2 x 1.5 V AAA/LR03
  • Dimensions: ok. 240 x 60 x 30 mm
  • Weight with batteries: ok. 0,2 kg
  • Working temperature: -10..+55°C
  • Storage temperature: -30°C..+70°C
  • the product meets the EMC requirements (immunity for industrial environment) according to the following standards EN 61326 – 1:2006 and EN 61326 – 2 – 2:2006